{"id":299,"date":"2026-09-29T05:30:32","date_gmt":"2026-09-29T05:30:32","guid":{"rendered":"https:\/\/chengguangenergy.com\/"},"modified":"2026-09-29T05:30:32","modified_gmt":"2026-09-29T05:30:32","slug":"ups-battery","status":"publish","type":"post","link":"https:\/\/chengguangenergy.com\/ru\/ups-battery\/","title":{"rendered":"UPS Battery: Backup &#038; Standby Battery Guide"},"content":{"rendered":"<p>A <strong>UPS (Uninterruptible Power Supply) battery<\/strong> holds a system up during a mains failure \u2014 bridging the gap until power returns or a generator starts. UPS duty is <strong>float service<\/strong>: the battery sits at a constant float voltage for months, then must deliver its rated capacity on demand, typically for 5\u201360 minutes.<\/p>\n<p>The correct battery for UPS duty is a sealed <strong>VRLA<\/strong> unit (AGM or GEL), not an automotive starting battery. Chengguang manufactures VRLA batteries for UPS, telecom, and standby applications, sized from small single blocks to full battery strings.<\/p>\n<h2>Key Takeaways<\/h2>\n<ul>\n<li><strong>Core rule<\/strong> \u2014 UPS is float service \u2014 use sealed VRLA (AGM\/GEL), never an automotive starting battery.<\/li>\n<li><strong>AGM vs GEL<\/strong> \u2014 AGM: any orientation + good high-rate discharge; GEL: best cycle life, upright only.<\/li>\n<li><strong>Temperature<\/strong> \u2014 Every 8\u201310 \u00b0C above 25 \u00b0C roughly halves VRLA design life.<\/li>\n<li><strong>Sizing<\/strong> \u2014 Account for Peukert \u2014 usable capacity drops below C20 at high discharge rates.<\/li>\n<\/ul>\n<h2>What UPS Duty Demands<\/h2>\n<table>\n<thead>\n<tr>\n<th>Requirement<\/th>\n<th>Why<\/th>\n<th>Battery Attribute<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Float service<\/td>\n<td>Battery held at charge for months\/years<\/td>\n<td>Low float current, low gassing<\/td>\n<\/tr>\n<tr>\n<td>No maintenance<\/td>\n<td>UPS sites are unattended<\/td>\n<td>Sealed VRLA, no watering<\/td>\n<\/tr>\n<tr>\n<td>High-rate discharge<\/td>\n<td>Minutes of backup at load<\/td>\n<td>Good high-rate performance<\/td>\n<\/tr>\n<tr>\n<td>Long design life<\/td>\n<td>Replacement is disruptive<\/td>\n<td>5\u201320 year design life (by grade)<\/td>\n<\/tr>\n<tr>\n<td>Safe indoor operation<\/td>\n<td>No acid spill or hydrogen venting<\/td>\n<td>VRLA sealed construction<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>VRLA Battery Types for UPS<\/h2>\n<table>\n<thead>\n<tr>\n<th>Type<\/th>\n<th>Electrolyte<\/th>\n<th>Characteristics<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>AGM<\/td>\n<td>Absorbed glass mat<\/td>\n<td>Any orientation, good high-rate, most common in UPS<\/td>\n<\/tr>\n<tr>\n<td>GEL<\/td>\n<td>Gelled (silica)<\/td>\n<td>Best cycle life, upright only<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<table>\n<thead>\n<tr>\n<th>VRLA Parameters (typical)<\/th>\n<th>Value<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Voltage<\/td>\n<td>12 V block or 2 V cell<\/td>\n<\/tr>\n<tr>\n<td>Capacity<\/td>\n<td>1.2\u2013200+ Ah<\/td>\n<\/tr>\n<tr>\n<td>Design life<\/td>\n<td>5\u201320 years (by grade)<\/td>\n<\/tr>\n<tr>\n<td>Float voltage<\/td>\n<td>2.25\u20132.30 V\/cell at 25 \u00b0C<\/td>\n<\/tr>\n<tr>\n<td>Operating temperature<\/td>\n<td>\u221215 \u00b0C to +50 \u00b0C<\/td>\n<\/tr>\n<tr>\n<td>Self-discharge<\/td>\n<td>&lt;2% per month at 20 \u00b0C<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h3>AGM vs GEL vs Flooded<\/h3>\n<table>\n<thead>\n<tr>\n<th>Feature<\/th>\n<th>AGM<\/th>\n<th>GEL<\/th>\n<th>Flooded<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Maintenance<\/td>\n<td>None<\/td>\n<td>None<\/td>\n<td>Periodic watering<\/td>\n<\/tr>\n<tr>\n<td>Orientation<\/td>\n<td>Any<\/td>\n<td>Upright only<\/td>\n<td>Upright only<\/td>\n<\/tr>\n<tr>\n<td>Cycle life<\/td>\n<td>Good<\/td>\n<td>Best<\/td>\n<td>Moderate<\/td>\n<\/tr>\n<tr>\n<td>High-rate discharge<\/td>\n<td>Good<\/td>\n<td>Moderate<\/td>\n<td>Excellent<\/td>\n<\/tr>\n<tr>\n<td>Relative cost<\/td>\n<td>$$<\/td>\n<td>$$$<\/td>\n<td>$<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>For UPS duty <strong>AGM is the default<\/strong>: any-orientation mounting, good high-rate response over the short autonomy window, and the lowest cost per Ah of the sealed chemistries. <strong>GEL<\/strong> is chosen where the UPS cycles daily (frequent outages) because it tolerates repeated deep discharge best \u2014 at the cost of upright-only mounting and slower recharge. Flooded automotive batteries are excluded outright.<\/p>\n<h2>Peukert: Usable Capacity at High Discharge<\/h2>\n<p>A VRLA block&#8217;s C20 rating assumes a gentle 20-hour discharge. UPS autonomy is minutes to a few hours, so the effective capacity is lower:<\/p>\n<table>\n<thead>\n<tr>\n<th>Discharge Rate<\/th>\n<th style=\"text-align: right;\">Usable Capacity (% of C20)<\/th>\n<th>Typical Duty<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>C20 (20-hour)<\/td>\n<td style=\"text-align: right;\">100%<\/td>\n<td>Long-duration standby<\/td>\n<\/tr>\n<tr>\n<td>C10 (10-hour)<\/td>\n<td style=\"text-align: right;\">~93%<\/td>\n<td>Telecom \/ general UPS<\/td>\n<\/tr>\n<tr>\n<td>C5 (5-hour)<\/td>\n<td style=\"text-align: right;\">~85%<\/td>\n<td>5-hour autonomy<\/td>\n<\/tr>\n<tr>\n<td>C1 (1-hour)<\/td>\n<td style=\"text-align: right;\">~65%<\/td>\n<td>Data-center UPS<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>At a 15-minute data-center autonomy, usable capacity derates further still. The block must be specified from the manufacturer&#8217;s <strong>discharge-rate table<\/strong>, never from the C20 label alone \u2014 this is the single most common UPS sizing error.<\/p>\n<h2>Starting Batteries vs UPS Batteries<\/h2>\n<p>An automotive SLI battery is the wrong tool for UPS duty. It is designed for seconds of high current and immediate recharge, not for months of float followed by a sustained moderate discharge \u2014 and it is not sealed, so it vents hydrogen and requires ventilation.<\/p>\n<table>\n<thead>\n<tr>\n<th>Attribute<\/th>\n<th>UPS (VRLA)<\/th>\n<th>Automotive SLI<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Float service<\/td>\n<td>Yes<\/td>\n<td>No<\/td>\n<\/tr>\n<tr>\n<td>Sealed \/ no maintenance<\/td>\n<td>Yes<\/td>\n<td>Maintenance-free (flooded)<\/td>\n<\/tr>\n<tr>\n<td>High-rate discharge<\/td>\n<td>Good<\/td>\n<td>Excellent (but short)<\/td>\n<\/tr>\n<tr>\n<td>Deep discharge tolerance<\/td>\n<td>Good<\/td>\n<td>Poor<\/td>\n<\/tr>\n<tr>\n<td>Design life<\/td>\n<td>5\u201320 years<\/td>\n<td>3\u20135 years<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Chengguang&#8217;s 14-model automotive catalog (SLI and heavy duty) is <strong>not<\/strong> intended for UPS standby duty. <strong>VRLA AGM and GEL batteries for UPS are manufactured to order<\/strong> under the OEM program, matched to your inverter\/rectifier float voltage and autonomy requirement.<\/p>\n<h2>Sizing a UPS Battery<\/h2>\n<ol>\n<li><strong>Determine the load<\/strong> in watts (W) and the required autonomy time (minutes\/hours).<\/li>\n<li><strong>Convert to Ah<\/strong> at the battery voltage: required Ah = (W \u00d7 hours) \u00f7 V \u00f7 0.8 (inverter efficiency).<\/li>\n<li><strong>Account for Peukert<\/strong> \u2014 at high discharge rates, usable capacity drops below the C20 rating (a C10 rating is ~93% of C20; a 1-hour rate can drop to ~65%).<\/li>\n<li><strong>Match float voltage<\/strong> to the UPS charger. A mismatch over-charges (thermal runaway) or under-charges (sulfation) the string.<\/li>\n<\/ol>\n<p><strong>Example:<\/strong> a 600 W load needing 30 minutes of autonomy at 12 V: (600 \u00d7 0.5) \u00f7 12 \u00f7 0.8 = <strong>31 Ah<\/strong> at the 0.5-hour rate \u2014 specify a VRLA block rated for that duty, not just its C20 figure.<\/p>\n<p><strong>String example \u2014 10 kVA data-center UPS.<\/strong> A 10 kVA UPS at 0.9 power factor drives a 9,000 W load. For 15 minutes of autonomy on a 48 V string: (9,000 \u00d7 0.25) \u00f7 48 \u00f7 0.9 = <strong>52 Ah<\/strong> at the 0.25-hour rate. A 52 Ah C20 block cannot supply 52 Ah in 15 minutes \u2014 at that rate its usable capacity is well below the C20 figure. Correct sizing: <strong>4\u00d7 12 V blocks (or 24\u00d7 2 V cells) in series<\/strong> per string, with each block&#8217;s 15-minute discharge rating \u2265 52 Ah; parallel a second string if one string cannot meet the per-block rating. String sizing is an electrical calculation, not a label lookup.<\/p>\n<h2>Buying Considerations<\/h2>\n<ol>\n<li><strong>Specify VRLA, not flooded.<\/strong> Indoor UPS sites require sealed, maintenance-free batteries.<\/li>\n<li><strong>Match design life to the budget.<\/strong> 5-year general-purpose blocks cost less; 10\u201320-year blocks suit telecom and data-center grade.<\/li>\n<li><strong>Replace full strings.<\/strong> Mixing old and new blocks in a series string causes imbalance and early failure.<\/li>\n<li><strong>Monitor temperature.<\/strong> Every 8\u201310 \u00b0C above 25 \u00b0C roughly halves VRLA design life \u2014 keep the battery room cool.<\/li>\n<\/ol>\n<h2>Float Service: The UPS Duty Cycle<\/h2>\n<p>A UPS battery spends its life in <strong>float service<\/strong> \u2014 held at a constant voltage just above its open-circuit voltage, waiting. The float setpoint is the critical number:<\/p>\n<table>\n<thead>\n<tr>\n<th>Parameter<\/th>\n<th>Value<\/th>\n<th>Why It Matters<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Float voltage<\/td>\n<td>2.25\u20132.30 V\/cell at 25 \u00b0C<\/td>\n<td>Too high = overcharge + water loss; too low = sulfation<\/td>\n<\/tr>\n<tr>\n<td>Float current<\/td>\n<td>Milliamps (trickle)<\/td>\n<td>Indicates a healthy, fully charged string<\/td>\n<\/tr>\n<tr>\n<td>Temperature<\/td>\n<td>25 \u00b0C nominal<\/td>\n<td>Every 8\u201310 \u00b0C above halves design life<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>A 12 V VRLA block floats at 13.5\u201313.8 V. The UPS rectifier\/charger must hold this setpoint precisely \u2014 a drift of even 0.5 V per string over-charges (thermal runaway) or under-charges (sulfation) the battery over months.<\/p>\n<h2>Thermal Runaway: The VRLA Failure Mode<\/h2>\n<p>Thermal runaway is the failure mode that makes VRLA dangerous if mis-charged: overcharging heats the battery, which lowers internal resistance, which increases charge current, which heats it further \u2014 a positive feedback loop that can end in case swelling or rupture.<\/p>\n<p>Prevention is entirely a matter of charging discipline:<\/p>\n<ol>\n<li><strong>Float at the correct voltage<\/strong> (temperature-compensated).<\/li>\n<li><strong>Keep the battery room cool<\/strong> \u2014 below ~30 \u00b0C.<\/li>\n<li><strong>Monitor float current<\/strong> \u2014 a rising float current on a healthy string is an early runaway signal.<\/li>\n<\/ol>\n<h2>Design Life by Grade<\/h2>\n<p>VRLA blocks are sold in service-life grades, and the spread is large:<\/p>\n<table>\n<thead>\n<tr>\n<th>Grade<\/th>\n<th>Design Life<\/th>\n<th style=\"text-align: right;\">Typical Application<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>General purpose<\/td>\n<td>3\u20135 years<\/td>\n<td style=\"text-align: right;\">Small UPS, emergency lighting<\/td>\n<\/tr>\n<tr>\n<td>\u0421\u0442\u0430\u043d\u0434\u0430\u0440\u0442\u043d\u044b\u0439<\/td>\n<td>5\u201310 years<\/td>\n<td style=\"text-align: right;\">Data-center UPS, telecom<\/td>\n<\/tr>\n<tr>\n<td>Premium<\/td>\n<td>10\u201320 years<\/td>\n<td style=\"text-align: right;\">Telecom core, substation, mission-critical<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Design life is measured at 25 \u00b0C float; operating hotter shortens it per the 8\u201310 \u00b0C rule. UPS strings are replaced on a schedule (3\u20135 years general purpose, 5\u201310+ premium) or when capacity testing shows the string below 80% of rated \u2014 whichever comes first.<\/p>\n<h2>VRLA Test Standards<\/h2>\n<p>UPS blocks are <strong>not<\/strong> tested to the automotive standards (SAE J537, EN 50342-1) that govern the starting-battery catalog. Stationary VRLA is tested to its own suite:<\/p>\n<table>\n<thead>\n<tr>\n<th>\u0421\u0442\u0430\u043d\u0434\u0430\u0440\u0442\u043d\u044b\u0439<\/th>\n<th>\u041e\u0431\u043b\u0430\u0441\u0442\u044c \u043f\u0440\u0438\u043c\u0435\u043d\u0435\u043d\u0438\u044f<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>IEC 60896-21<\/td>\n<td>Stationary VRLA \u2014 test methods (capacity, float current, high-rate)<\/td>\n<\/tr>\n<tr>\n<td>IEC 60896-22<\/td>\n<td>Stationary VRLA \u2014 requirements<\/td>\n<\/tr>\n<tr>\n<td>IEEE 1188<\/td>\n<td>Telecom VRLA \u2014 maintenance, testing &amp; replacement<\/td>\n<\/tr>\n<tr>\n<td>IEC 61056<\/td>\n<td>General-purpose lead-acid blocks (small UPS, emergency lighting)<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Key acceptance tests: C10\/C20 capacity, float current, high-rate discharge, internal resistance, and thermal-runaway sensitivity. Confirm which standard a manufacturer quotes before comparing two UPS blocks \u2014 a &#8220;C10&#8221; figure and a &#8220;C20&#8221; figure are not the same rating.<\/p>\n<h2>UPS Battery Monitoring &amp; Testing<\/h2>\n<p>A VRLA string degrades invisibly until it fails \u2014 the only way to catch it early is scheduled testing:<\/p>\n<table>\n<thead>\n<tr>\n<th>Test<\/th>\n<th>Method<\/th>\n<th>Cadence<\/th>\n<th>Action Trigger<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Float current<\/td>\n<td>Measure trickle current per block<\/td>\n<td>Monthly<\/td>\n<td>Rising float current = early warning<\/td>\n<\/tr>\n<tr>\n<td>Impedance \/ conductance<\/td>\n<td>Internal-resistance meter<\/td>\n<td>Quarterly<\/td>\n<td>&gt;30% deviation from baseline = replace<\/td>\n<\/tr>\n<tr>\n<td>Capacity test<\/td>\n<td>Discharge to 80% at rated load<\/td>\n<td>Annually<\/td>\n<td>&lt;80% of rated = replace string<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Impedance testing is the most practical field method: rising internal resistance tracks plate degradation long before a capacity test would fail. Replace blocks or the full string at 80% of rated capacity \u2014 never mix old and new blocks in a series string.<\/p>\n<h2>UPS Runtime vs Load \u2014 Reference<\/h2>\n<p>Runtime is load-dependent, not a fixed number. A 100 Ah (C20) VRLA string delivers roughly:<\/p>\n<table>\n<thead>\n<tr>\n<th>Load<\/th>\n<th style=\"text-align: right;\">Effective Capacity<\/th>\n<th style=\"text-align: right;\">Approx. Runtime<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>5 A (C20)<\/td>\n<td style=\"text-align: right;\">~100 Ah<\/td>\n<td style=\"text-align: right;\">~20 hours<\/td>\n<\/tr>\n<tr>\n<td>25 A (C5)<\/td>\n<td style=\"text-align: right;\">~85 Ah<\/td>\n<td style=\"text-align: right;\">~3.4 hours<\/td>\n<\/tr>\n<tr>\n<td>50 A (C2)<\/td>\n<td style=\"text-align: right;\">~70 Ah<\/td>\n<td style=\"text-align: right;\">~1.4 hours<\/td>\n<\/tr>\n<tr>\n<td>100 A (C1)<\/td>\n<td style=\"text-align: right;\">~65 Ah<\/td>\n<td style=\"text-align: right;\">~39 minutes<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>These are Peukert-de-rated figures \u2014 a 100 Ah block does not deliver 100 Ah at a 1-hour rate. Size the string for the actual load and autonomy, then specify the block from the manufacturer&#8217;s discharge-rate table.<\/p>\n<h2>Frequently Asked Questions<\/h2>\n<p><strong>Can I use a car battery in a UPS?<\/strong> No. Automotive SLI batteries are not sealed, not built for float service, and will fail early in UPS duty. Use a VRLA (AGM\/GEL) battery.<\/p>\n<p><strong>How often should UPS batteries be replaced?<\/strong> Every 3\u20135 years for general-purpose grade and 5\u201310+ years for premium grade \u2014 or when capacity testing shows the string below 80% of rated.<\/p>\n<p><strong>Why do UPS batteries fail in hot rooms?<\/strong> Every 8\u201310 \u00b0C above 25 \u00b0C roughly halves VRLA design life. Keep the battery room cool and ventilated.<\/p>\n<p><strong>How do I test a UPS battery?<\/strong> Quarterly impedance\/conductance testing plus an annual discharge capacity test. Replace the string when any block shows &gt;30% internal-resistance deviation or the string falls below 80% of rated capacity.<\/p>\n<p><strong>Why replace the whole string at once?<\/strong> Mixing old and new blocks in a series string causes charge imbalance \u2014 the new block overcharges while the old one undercharges, and both fail early.<\/p>\n<h2>Related Articles<\/h2>\n<ul>\n<li><a href=\"\/ru\/deep-cycle-battery\/\">Deep Cycle Battery Guide<\/a><\/li>\n<li><a href=\"\/ru\/solar-storage-battery\/\">Solar Storage Battery Guide<\/a><\/li>\n<li><a href=\"\/ru\/agm-battery\/\">AGM Battery Guide<\/a><\/li>\n<li><a href=\"https:\/\/technical.chengguangenergy.com\/battery-technology\/vrla\/\" rel=\"nofollow\">VRLA Battery Technology Reference<\/a><\/li>\n<li><a href=\"https:\/\/technical.chengguangenergy.com\/battery-testing\/c20-capacity\/\" rel=\"nofollow\">C20 Capacity \u2014 Complete Guide<\/a><\/li>\n<li><a href=\"https:\/\/chengguangenergy.com\/ru\/contact\/\">Request UPS OEM Quote<\/a><\/li>\n<\/ul>\n<h2>Sources &amp; Verification<\/h2>\n<p>Specifications on this page are sourced from Chengguang Power Tech factory technical documentation and tested to JIS D 5301, DIN EN 50342-1, SAE J537, and IEC 60095-1. Contact Chengguang for the exact data sheet. Every batch ships with a Certificate of Analysis (CoA).<\/p>\n<p><em>Author: Chengguang Engineering Team \u00b7 Reviewed: IATF 16949 Quality Department \u00b7 Last updated: 2026-08-19<\/em><\/p>","protected":false},"excerpt":{"rendered":"<p>UPS battery guide \u2014 why VRLA not automotive for float service, AGM vs GEL, sizing a UPS battery with Peukert, and design life by grade.<\/p>","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_kad_post_transparent":"","_kad_post_title":"","_kad_post_layout":"","_kad_post_sidebar_id":"","_kad_post_content_style":"","_kad_post_vertical_padding":"","_kad_post_feature":"","_kad_post_feature_position":"","_kad_post_header":false,"_kad_post_footer":false,"_kad_post_classname":"","footnotes":"","_llm_markdown_disabled":false},"categories":[125],"tags":[],"class_list":["post-299","post","type-post","status-publish","format-standard","hentry","category-battery-technology"],"_links":{"self":[{"href":"https:\/\/chengguangenergy.com\/ru\/wp-json\/wp\/v2\/posts\/299","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/chengguangenergy.com\/ru\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/chengguangenergy.com\/ru\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/chengguangenergy.com\/ru\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/chengguangenergy.com\/ru\/wp-json\/wp\/v2\/comments?post=299"}],"version-history":[{"count":1,"href":"https:\/\/chengguangenergy.com\/ru\/wp-json\/wp\/v2\/posts\/299\/revisions"}],"predecessor-version":[{"id":802,"href":"https:\/\/chengguangenergy.com\/ru\/wp-json\/wp\/v2\/posts\/299\/revisions\/802"}],"wp:attachment":[{"href":"https:\/\/chengguangenergy.com\/ru\/wp-json\/wp\/v2\/media?parent=299"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/chengguangenergy.com\/ru\/wp-json\/wp\/v2\/categories?post=299"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/chengguangenergy.com\/ru\/wp-json\/wp\/v2\/tags?post=299"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}